Safety Engineering

The effect of opening position on pool-fire suppression by water mist in a compartment

Expand
  • Fire Engineering Department,Chinese People′s Armed Police Forces Academy,Langfang Hebei,065000

Received date: 2013-03-25

Abstract

Experiments have been carried out to investigate the effect of opening position on pool-fire suppression by water mist in a compartment.The results show that no matter whether the opening is located at the wall or the ceiling,the extinguishing time of the pool-fire increases with the opening area,and decreases with the HRR of the pool-fire.When the HRR of the pool-fire is lower than a critical value,the extinguishing time for wall opening case is longer than that for ceiling opening case.And the extinguishing time for the case of wall opening is less than that for ceiling opening case otherwise.Theoretical analysis shows that the differences in abilities of mass exchange inside and outside and abilities of storing smoke under the ceiling should be responsible for the differences in extinguishing time between the two cases.

Cite this article

DU Wen-feng,DAI Shi-jie . The effect of opening position on pool-fire suppression by water mist in a compartment[J]. Journal of Shenyang Aerospace University, 2013 , 30(3) : 61 -64 . DOI: 10.3969/j.issn.2095-1248.2013.03.013

References

[1]陈兵.船舶顶部开口舱室油油盘火灾模拟实验研究[D].合肥:中国科学技术大学,2011.
[2]Chow W.K,Li Y.F.A review on studying extinguishing room fires by water mist[J].Journal of Applied Fire Science,2003,11(4):367-403.
[3]Takeda H.Model experiments of ship fire[C].In Proceeding of the 22nd Symposium (International) on Combustion.1989.Pittsburgh,PA:The Combustion Institute.
[4]Liu Z,Kim,A.K.A Review of water mist fire suppression systems-fundamental studies.[R].NRCC.2000.1.
[5]Vaari J.A Transient one-zone computer model for total flooding water mist fire suppression in ventilated enclosures[J].Fire Safety Journal,2002,37(3):229-257.
[6]Kim K I,Ohtani H,Uehara Y.Experimental study on oscillating behavior in a small-scale compartment fire[J].Fire Safety Journal,1993,20(4):377-384.
[7]Liu Z,Kim A K.The effect of air convection on the performance of water mist fire suppression systems[R].ASME Proceedings of the Seventh AIAA/ASME Joint Thermophysics and Heat Transfer Conference,1998:227-236.
[8]杜文锋,戴士杰.顶棚水平开口对细水雾灭室内火的影响研究[J].消防科学与技术,2013,32(3):280-293.